Protective Relaying for Power Generation Systems provides both a general overview and in-depth discussion of each topic, making it easy to tailor the material to students' needs.
Features:
- Examines the protection of generators and motors at a level of depth not found in more general texts on the subject
- Offers discussions unavailable elsewhere, such as time decrement generator fault calculations and minimum excitation limit
- Includes steady state and dynamic stability limits
- Discusses protective components in detail, emphasizing potential for damage such as rotor and turbine blade heating
- Presents theoretical discussions along with examples that provide quick how-to information
- Includes Excel® and Mathcad® workbook constructions for performing protection-related calculations including CT saturation analysis and power system swings
Contents
Generator Normal Operations
- The Sample System
- Generator Capability
- Voltage Limitations
- System Limitations
- Generator Capability Variations with Voltage
- Excitation System
Generator Short Circuit Calculations
- Short-Circuit Current Characteristics
- Generator Internal Magnetics
- Generator Magnetic Structures
- Generator Constants
- Fault Current Calculations
- Voltage Regulator
- Practical Shortcuts
- Short Circuit Calculation Example
Generator Differential Relay: 87G
- Ideal Differential Relay
- Practical Considerations
- Percentage Differential Relay
- Relay Characteristics
- Minimum Operating Current Setting
- Slope Setting
- Sample System Differential Relay Settings
- CT Saturation
- Stabilizing Resistor
- Balancing Burden
- Time Delay
- Frequency Response
Backup Fault Protection
- Purpose and Implementation
- Voltage Supervised Overcurrent Relays
- Distance Relays
Generator Ground Fault Protection
- Generator Grounding Considerations
- Methods of Grounding
- Ground Fault Protection
Unbalanced Current Protection
- What is Negative-Sequence Current?
- Effects of Negative-Sequence Current
- Generator Negative-Sequence Capability
- Sources of Negative-Sequence Current
- In-Service (I2)^2t Duty Versus Standards
- Unbalanced Current Protection
- Negative-Sequence Relay Settings
Motoring Protection
- Effects of Motoring
- Protection
- Sequential Trip Logic
- Backup Protection
- Setting Device 32
- Applying Reversed Power Relay on the Sample System
Field Winding Protection
- Field Ground Protection
- Field Overcurrent Protection
- Settings for Field Overcurrent Overvoltage Relays
- Applying Field OC Protection on the Sample System
Overexcitation
- Causes of Overexcitation
- Damage
- V/Hz Limits
- Protection
- Settings
- Differential Relay Response to Overexcitation
- Application of V/Hz Protection on the Sample System
Abnormal Frequency Protection
- Effect on Generator
- Steam Turbines
- Combustion Turbines
- Hydro Generators
- Excitation System
- Protection and Settings
Minimum Excitation Limiter
- Overview of the Minimum Excitation Limiter Application
- Setting Criteria Background
- Setting Criteria
- Steady State and Dynamic Stability Considerations
- Generator Leading VAR Capability
- Coordination with the LOF Relay
- System Stability Limits
- MEL Protective Characteristic
- MEL Dynamic Performance
- MEL Application on the Sample System
Loss of Synchronism
- Turbine Generator Damage
- Transient Stability
- Out-of-Step Protection
- Classical Swing Impedance Characteristic
- Dynamic Swing Representation
- Dynamic Swing Calculations
- Setting Consideration
- Out-of-Step Relay: Device 78
- Setting Out-of-Step on Sample System
Loss of Field Protection
- System Impact
- Generator Damage
- Loss of Field Protection: Device 40
- Distance Relay Schemes
- Other Causes for LOF Relay Operations
- LOF Relays During System Disturbances
- Special Considerations for Hydro Units
- Application of the LOF on the Sample System
Synchronization Protection
- Damage
- Synchronizing Methods
- Synchronism Check Relays (Device 25)
- Automatic Synchronizer (Device 25A)
- Slow Breaker Protection
- Settings
- Synchronizing Equipment on the Sample System
Accidental Energization Protection
- Generator State at Energization
- Inadvertent Energization
- Breaker Flashover
- Dynamic Analysis of Three-Phase Energization from Standstill
- Generator Damage
- Turbine Damage
- Energization Protection
- Protection Provided by Native Schemes
- Dedicated Energization Protection
- Applying Energization Protection on the Sample System
Motor Protection
- Motor Characteristics And Representation
- Motor Ratings
- Motor Characteristics
- Motor Applications
- Motor Starting
- Mechanic System Considerations
- Pump Characteristics
- Motor Overload Protection
- Multifunction Microprocessor Relays
- Transient Current Evaluation
- Special Schemes for Difficult Starts
- Direct Temperature Measurement
- Phase Fault Protection
- Ground Fault Protection
- Phase Unbalanced Protection
- Sample Setting Calculations
Index